Does Coil Coating Affect EER and COP Ratings?

Key facts

Key facts: Does Coil Coating Affect EER and COP Ratings?
FactorEffect on efficiency
Thin film (5–15 μm)Small; PG-S1 tested at up to 1.8% heat-transfer loss
Thick film (20–40 μm and above)Larger; test on a comparable coil
Bridged finsLower airflow and capacity; the largest effect
Uncoated coil corroding in serviceEfficiency falls as fins corrode and foul

Where efficiency is lost

EER and COP compare cooling or heating output with power input. A coating can lower output by adding thermal resistance and raise power by increasing fan pressure drop. With a thin film both effects are small.

Ratings and coated units

Efficiency ratings are measured under standard conditions on the unit the manufacturer submits. A coating added afterwards is not part of that test. Some manufacturers publish derating guidance for coated coils; ask before relying on rated values in energy calculations.

Over the life of the unit

An uncoated coil in a corrosive site loses capacity as fins corrode, loosen and foul. Over several years that loss usually exceeds the initial effect of a thin coating.

What this means for your project

Specify a thin-film system and a film range, ask for heat-transfer data, and check the manufacturer’s position on coated units if rated efficiency is contractual.