How Thick Should HVAC Coil Coating Be?

Key facts

Key facts: How Thick Should HVAC Coil Coating Be?
SystemDry filmTypical use
PG-S15–15 μmCoastal and industrial coils, dip before shipment
PG-S25–10 μmAluminium radiators, bakeable heat exchangers
PG-W5–10 g/m² per sideCoil lines, mild coastal and humid sites
PG-C20–40 μmComplete units, chemical and wastewater sites

Thickness follows chemistry

Each coating system is designed for a film range. A sol-gel system at 5–15 μm forms a dense, hard film; a two-component air-dry system needs 20–40 μm to reach its barrier properties. Comparing thicknesses across systems says little on its own.

Coverage beats thickness

A thin film that reaches every collar and joint protects better than a thick film that misses them. Dip application gives full coverage at thin film; spray builds thickness on faces and less inside.

The cost of going thicker

Thick films add thermal resistance, and at high fin density they bridge the gaps between fins. The resulting loss in capacity and airflow lasts for the life of the coil.

What this means for your project

Specify a film range for the chosen system, how it is measured and where. Ask for the batch film thickness record rather than a single nominal value.